Total-flood and local-application CO₂ for enclosed plant where water would do the damage the fire did not. Design, supply, installation, testing and commissioning.

Installation photo — CO₂ cylinder bank and manifold in a plant room
Scope
Survey → commissioning → AMC
Practice
IS 6382 · NBC 2016 Pt.4
Typical use
Switch rooms, generator rooms
What it is

It removes the oxygen, which is why the room has to be empty

Carbon dioxide puts a fire out by displacing the oxygen it needs. That works on energised electrical equipment and on flammable liquids, and it leaves nothing behind to clean up — but at the concentration required it will not sustain a person, so a CO₂ system is for spaces that are normally unoccupied and it is designed around getting people out first.

The quantity comes from the volume of the enclosure and how well that enclosure holds gas. Openings, cable entries and ventilation ducts all have to be closed or accounted for, because a room that leaks will not hold concentration long enough to be sure the fire is out. Where the risk is a machine rather than a room — a press, a dip tank, a turbine — a local-application design puts the gas on the object instead of filling the space.

Commissioning is where these systems are made safe rather than just installed. We prove the detection and release sequence, the pre-discharge alarm and its delay, the abort and manual release, the damper and fan shutdown interlocks, and the door signage and lock-off arrangement — then hand over the discharge calculation and the operating instructions the room needs posted at its entrance.

Equipment

What the installation is built from

A CO₂ installation is a cylinder bank, a distribution network and a releasing sequence that protects the people before it protects the plant.

Cylinder bank and manifoldHigh-pressure cylinders sized to the enclosure, with the manifold, check valves and flexible discharge hoses.
Master and slave valve actuatorsElectrical and pneumatic actuation, so one released cylinder fires the bank.
Selector valves for multiple risksOne bank protecting several enclosures, directing the discharge to the one that called for it.
Discharge nozzles and pipeworkSized and orificed by calculation, positioned to fill the enclosure or to hit the object.
Releasing panel with abort and manual releaseRuns the detection, the delay and the alarm, and gives a person in the room a way to stop it.
Pre-discharge alarm and door signageSounder and beacon inside and outside, and the warning plates at every entrance.
Damper, fan and shutter interlocksThe enclosure has to close before the gas arrives, or the concentration never holds.
Cylinder pressure and weight supervisionSo a bank that has lost charge is reported rather than assumed to be ready.

Tell us about the project

Send the drawings or the BOQ and we will price it line by line. Most enquiries start with a site visit, because the site decides the system — not the catalogue.